EIGENROOMLAB WORKSHEET 36Water tank

Replace water lost to a drain

NameSectionDate

Goal

Compare a fixed pump command with PI level control when an extra drain opens.

Setup

Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:

Tank area A
0.1 m²
Outlet coefficient c
0.003 m⁵ᐟ²/s
Linearization height h₀
0.5 m
Initial height
0.5 m
Target height
0.5 m
Pump control
PI + q₀ bias
Flow step Δq
0 m³/s
Pump limit
0.005 m³/s
Kp
0.004 m²/s
Ki
0.00015 m²/s²
Anti-windup
On
Extra drain from 30 s
0.0008 m³/s
  1. APreset, exactly as the link opens it.
  2. BChange only: Pump control → Manual step about q₀.

Pin each run before you change a setting, so you can compare runs at the same replay time.

1. Predict

An extra drain opens at 30 s. Will fixed pump flow and PI react in the same way?

Write your prediction and a reason before you run anything.

2. Observe

Read each value in the lab and write it in the table.

QuantityWhere to read itAB
Nonlinear height at t = 60 s (m)Readout at 60 s
Nonlinear height at t = 120 s (m)Readout at 120 s
Pump flow at t = 120 s (m³/s)Readout at 120 s
Integral contribution at t = 120 s (m³/s)Readout at 120 s
Final target error (m)Results below the plots

3. Explain

  1. Compare the pump flow at 120 s. Which run replaced the lost water?

  2. Run A is still below its target at 120 s. Is that a steady-state error?

Extension (optional)

Raise Ki to 0.0003 m²/s² (run C). How close to the target does the level end?