EIGENROOMLAB WORKSHEET 36Water tank
Replace water lost to a drain
NameSectionDate
Goal
Compare a fixed pump command with PI level control when an extra drain opens.
Setup
Lab eigenroom.com/lab/tank?lesson=tank-disturbance · short link eigenroom.com/tank-disturbance
Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:
- Tank area A
- 0.1 m²
- Outlet coefficient c
- 0.003 m⁵ᐟ²/s
- Linearization height h₀
- 0.5 m
- Initial height
- 0.5 m
- Target height
- 0.5 m
- Pump control
- PI + q₀ bias
- Flow step Δq
- 0 m³/s
- Pump limit
- 0.005 m³/s
- Kp
- 0.004 m²/s
- Ki
- 0.00015 m²/s²
- Anti-windup
- On
- Extra drain from 30 s
- 0.0008 m³/s
- APreset, exactly as the link opens it.
- BChange only: Pump control → Manual step about q₀.
Pin each run before you change a setting, so you can compare runs at the same replay time.
1. Predict
An extra drain opens at 30 s. Will fixed pump flow and PI react in the same way?
Write your prediction and a reason before you run anything.
2. Observe
Read each value in the lab and write it in the table.
| Quantity | Where to read it | A | B |
|---|---|---|---|
| Nonlinear height at t = 60 s (m) | Readout at 60 s | ||
| Nonlinear height at t = 120 s (m) | Readout at 120 s | ||
| Pump flow at t = 120 s (m³/s) | Readout at 120 s | ||
| Integral contribution at t = 120 s (m³/s) | Readout at 120 s | ||
| Final target error (m) | Results below the plots |
3. Explain
Compare the pump flow at 120 s. Which run replaced the lost water?
Run A is still below its target at 120 s. Is that a steady-state error?
Extension (optional)
Raise Ki to 0.0003 m²/s² (run C). How close to the target does the level end?