EIGENROOMLAB WORKSHEET 29Thermal control

A target beyond heater power

NameSectionDate

Goal

Watch an integrator wind up behind a heater that cannot reach its target, and measure what anti-windup prevents.

Setup

Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:

Heat capacity C
1000 J/K
Heat loss H
5 W/K
Ambient Ta
20 °C
Initial temperature
20 °C
Target temperature
100 °C
Maximum heater
200 W
Controller
PI
Kp
20 W/K
Ki
0.1 W/(K·s)
Conditional anti-windup
On
Event
Target change to 40 °C at 300 s
Duration
900 s
  1. APreset, exactly as the link opens it.
  2. BChange only: Conditional anti-windup → Off.

Pin each run before you change a setting, so you can compare runs at the same replay time.

1. Predict

With 200 W maximum and 5 W/K heat loss, the highest equilibrium is 60 °C. What happens if you ask for 100 °C, then reduce the target to 40 °C at 300 s?

Write your prediction and a reason before you run anything.

2. Observe

Read each value in the lab and write it in the table.

QuantityWhere to read itAB
Temperature at t = 299 s (°C)Readout at 299 s
Integral term at t = 301 s (W)Readout at 301 s
Applied power at t = 330 s (W)Readout at 330 s
Temperature at t = 600 s (°C)Readout at 600 s
Final target − temperature (°C)Results below the plots

3. Explain

  1. Neither run reaches the target before 300 s. What is the highest temperature this heater can hold?

  2. After the target drops at 300 s, why does run B keep heating at full power?

Extension (optional)

Set a reachable target of 50 °C with no event, and compare anti-windup off (run C) and on (run D). Does windup still matter?

Source: eigenroom.com/worksheets/thermal/thermal-windupCite: EIGENROOM. (2026). A target beyond heater power [Lab worksheet]. Accessed YYYY-MM-DD. https://eigenroom.com/worksheets/thermal/thermal-windup