EIGENROOMLAB WORKSHEET 29Thermal control
A target beyond heater power
NameSectionDate
Goal
Watch an integrator wind up behind a heater that cannot reach its target, and measure what anti-windup prevents.
Setup
Lab eigenroom.com/lab/thermal?lesson=thermal-windup · short link eigenroom.com/thermal-windup
Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:
- Heat capacity C
- 1000 J/K
- Heat loss H
- 5 W/K
- Ambient Ta
- 20 °C
- Initial temperature
- 20 °C
- Target temperature
- 100 °C
- Maximum heater
- 200 W
- Controller
- PI
- Kp
- 20 W/K
- Ki
- 0.1 W/(K·s)
- Conditional anti-windup
- On
- Event
- Target change to 40 °C at 300 s
- Duration
- 900 s
- APreset, exactly as the link opens it.
- BChange only: Conditional anti-windup → Off.
Pin each run before you change a setting, so you can compare runs at the same replay time.
1. Predict
With 200 W maximum and 5 W/K heat loss, the highest equilibrium is 60 °C. What happens if you ask for 100 °C, then reduce the target to 40 °C at 300 s?
Write your prediction and a reason before you run anything.
2. Observe
Read each value in the lab and write it in the table.
| Quantity | Where to read it | A | B |
|---|---|---|---|
| Temperature at t = 299 s (°C) | Readout at 299 s | ||
| Integral term at t = 301 s (W) | Readout at 301 s | ||
| Applied power at t = 330 s (W) | Readout at 330 s | ||
| Temperature at t = 600 s (°C) | Readout at 600 s | ||
| Final target − temperature (°C) | Results below the plots |
3. Explain
Neither run reaches the target before 300 s. What is the highest temperature this heater can hold?
After the target drops at 300 s, why does run B keep heating at full power?
Extension (optional)
Set a reachable target of 50 °C with no event, and compare anti-windup off (run C) and on (run D). Does windup still matter?