EIGENROOMLAB WORKSHEET 07ANSWER KEY · FOR INSTRUCTORSDC motor · PID tuning

Push back against a load

Goal

Measure how far a short load pulse pushes the speed and how the feedback voltage answers it.

Setup

Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:

Target speed
120 rad/s
Loop
Closed loop
Controller type
PID
Proportional Kp
0.22
Integral Ki
0.6
Derivative Kd
0.008
Anti-windup
On
Load torque
0.04 N·m
Sensor noise
0
Controller period
20 ms
Disturbance events
None
Recording
12 s
  1. APreset, exactly as the link opens it.
  2. BChange only: Disturbance events → Tap load 0.06 N·m at 4 s for 0.25 s. Replay to 4 s and press Tap load, then check that the event list matches this run's settings.
  3. CChange only: Disturbance events → Step load 0.06 N·m from 4 s. (ext.)

1. Predict

How does the loop recover when the shaft load increases?

What happens

A short load pulse slows the motor. Feedback raises voltage, then relaxes when the pulse ends.

2. Observe

QuantityWhere to read itABC ext.
Lowest speed, 4–6 s (rad/s)Plot, with the replay cursor119.8 rad/s114.8 rad/s114.0 rad/s
Highest applied voltage, 4–6 s (V)Control effort plot10.0 V11.7 V12.0 V
Settling, ±2% of target (s)Measured response1.88 s4.38 sNot settled
Final error (rad/s)Measured response0.00 rad/s0.00 rad/s6.04 rad/s

Values computed by DC motor and cart-pole engine 1.5.0 at the settings above. A replay readout can differ in the last digit if the slider is not exactly at the stated time; values read from a plot are approximate.

3. Explain

  1. How far does the speed fall during the tap, and what does the applied voltage do?

    The speed dips to 114.8 rad/s, against 119.8 rad/s without the tap. Feedback raises the applied voltage to 11.7 V (run A: 10.0 V), then relaxes when the pulse ends.

  2. The target is the same in both runs. Why does the settling time change?

    Settling is the time after which the speed stays inside ±2% of the target. The tap pushes the speed out of that band after 4 s, so settling moves from 1.88 s to 4.38 s. A settling time measured on a target step says nothing about recovery from a load.

Extension (optional)

Replace the tap with a Step load of the same size at 4 s (run C). Does the speed return to the target?

Not fully. Holding the target against the extra load would need more than 12 V: the applied voltage stays at 12.0 V and the run ends 6.04 rad/s short of the target, at 114.0 rad/s.

Source: eigenroom.com/worksheets/motor/disturbance/answersCite: EIGENROOM. (2026). Push back against a load [Lab worksheet]. Accessed YYYY-MM-DD. https://eigenroom.com/worksheets/motor/disturbance