EIGENROOMLAB WORKSHEET 02DC motor · Feedback basics
Open loop versus closed loop
NameSectionDate
Goal
Show with one load step that only a feedback command reacts to the speed change the load causes.
Setup
Lab eigenroom.com/lab?lesson=open-closed-loop · short link eigenroom.com/open-closed-loop
Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:
- Target speed
- 100 rad/s
- Loop
- Closed loop
- Controller type
- PID
- Proportional Kp
- 0.22
- Integral Ki
- 0.6
- Derivative Kd
- 0.008
- Anti-windup
- On
- Load torque
- 0 N·m
- Sensor noise
- 0
- Controller period
- 20 ms
- Disturbance events
- Step load 0.04 N·m from 4 s
- Recording
- 12 s
- APreset, exactly as the link opens it.
- BChange only: Loop → Open loop, 7 V. Pin run A, then switch Loop to Open loop. Leave the manual voltage as the preset sets it.
Pin each run before you change a setting, so you can compare runs at the same replay time.
1. Predict
At 4 s, a load increases. Which command reacts to the resulting speed error?
Write your prediction and a reason before you run anything.
2. Observe
Read each value in the lab and write it in the table.
| Quantity | Where to read it | A | B |
|---|---|---|---|
| Speed at t = 3.9 s (rad/s) | Readout at 3.9 s | ||
| Speed at t = 12 s (rad/s) | Readout at 12 s | ||
| Applied voltage at t = 12 s (V) | Readout at 12 s | ||
| Final error (rad/s) | Measured response |
3. Explain
How far does each run's speed fall between t = 3.9 s and t = 12 s? Which voltage command reacted to the load?
Once the closed-loop error is back to zero, which term of the PID controller holds the extra voltage the load needs?
Extension (optional)
Double the load event in both runs (runs C and D). Does the closed loop still return to the target? The actuator can apply at most 12 V.