EIGENROOMLAB WORKSHEET 31ANSWER KEY · FOR INSTRUCTORSState feedback & observer
Move the closed-loop poles
Goal
Place the closed-loop poles of a mass–spring–damper and measure the force a faster design asks for.
Setup
Lab eigenroom.com/lab/state-feedback?lesson=place-poles · short link eigenroom.com/place-poles
Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:
- Controller ωn
- 2 rad/s
- Controller damping ζ
- 0.7
- Observer speed ratio
- 2
- Feedback state
- True state
- Target position
- 0.2 m
- Initial position
- 0 m
- Initial estimate error
- 0.3 m
- Position noise amplitude
- 0 m
- Force limit
- 10 N
- APreset, exactly as the link opens it.
- BChange only: Controller ωn → 4 rad/s.
- CChange only: Controller ωn → 6 rad/s.
- DChange only: Controller ωn → 6 rad/s, Target position → 0.5 m. (ext.)
1. Predict
Does doubling the desired natural frequency improve speed without any cost?
K is calculated from the desired second-order polynomial. Faster nominal poles increase the required feedback and reference gains. The ±10 N actuator can clip the request, so the actual response need not follow those poles. Pole placement describes the unsaturated, exact-model linear loop.
2. Observe
| Quantity | Where to read it | A | B | C | D ext. |
|---|---|---|---|---|---|
| Requested force at t = 0 s (N) | Readout at 0 s | 0.8 N | 3.2 N | 7.2 N | 18 N |
| Position at t = 0.5 s (m) | Readout at 0.5 s | 0.061189 m | 0.14514 m | 0.19306 m | 0.47133 m |
| Position at t = 1 s (m) | Readout at 1 s | 0.14514 m | 0.20832 m | 0.20392 m | 0.51108 m |
| Clipped command time (s) | Results below the plots | 0 s | 0 s | 0 s | 0.092 s |
Values computed by State-feedback, tank and RLC engine 1.0.0 at the settings above. A replay readout can differ in the last digit if the slider is not exactly at the stated time; values read from a plot are approximate.
3. Explain
How does the force requested at t = 0 s grow with ωn, and why?
0.8 N, 3.2 N and 7.2 N. At t = 0 the state is zero, so the request is N·r with the reference gain N = ωn²: doubling ωn quadruples it.
None of these runs reaches the force limit. What happens to the pole-placement design once the request exceeds it?
Clipped time is 0 s even in run C. Once the request exceeds the limit, the actuator delivers less than the design assumes, the loop no longer has the placed poles, and the response stops following them.
Extension (optional)
Keep ωn = 6 rad/s and raise the target position to 0.5 m (run D). How long is the command clipped?
The request at t = 0 s is 18 N against a limit of 10 N, and the command is clipped for 0.092 s. During that time the response is slower than the placed poles predict.