EIGENROOMLAB WORKSHEET 34Water tank
A tangent is a local model
NameSectionDate
Goal
Test where a tangent (linearized) model of a draining tank stops predicting the real level.
Setup
Lab eigenroom.com/lab/tank?lesson=local-tank-model · short link eigenroom.com/local-tank-model
Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:
- Tank area A
- 0.1 m²
- Outlet coefficient c
- 0.003 m⁵ᐟ²/s
- Linearization height h₀
- 0.5 m
- Initial height
- 0.5 m
- Target height
- 0.8 m
- Pump control
- Manual step about q₀
- Flow step Δq
- 0.0002 m³/s
- Pump limit
- 0.005 m³/s
- Kp
- 0.004 m²/s
- Ki
- 0.00003 m²/s²
- Anti-windup
- On
- Extra drain from 30 s
- 0 m³/s
- APreset, exactly as the link opens it.
- BChange only: Flow step Δq → 0.0015 m³/s.
Pin each run before you change a setting, so you can compare runs at the same replay time.
1. Predict
Will a linear model around h₀ = 0.5 m match both a small and a large flow change?
Write your prediction and a reason before you run anything.
2. Observe
Read each value in the lab and write it in the table.
| Quantity | Where to read it | A | B |
|---|---|---|---|
| Nonlinear height at t = 30 s (m) | Readout at 30 s | ||
| Nonlinear height at t = 120 s (m) | Readout at 120 s | ||
| Linear prediction at t = 120 s (m) | Readout at 120 s | ||
| Nonlinear − linear height at t = 120 s (m) | Readout at 120 s |
3. Explain
How well does the tangent model predict each run at 120 s?
Which way is the linear model wrong in run B, and why?
Extension (optional)
Try Δq = -0.0015 m³/s, a large decrease (run C). Which way is the linear model wrong now?