EIGENROOMLAB WORKSHEET 35ANSWER KEY · FOR INSTRUCTORSWater tank

The same tank has different time scales

Goal

Compare the same tank's local time constant and gain at two operating heights.

Setup

Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:

Tank area A
0.1 m²
Outlet coefficient c
0.003 m⁵ᐟ²/s
Linearization height h₀
0.5 m
Initial height
0.5 m
Target height
0.8 m
Pump control
Manual step about q₀
Flow step Δq
0.0002 m³/s
Pump limit
0.005 m³/s
Kp
0.004 m²/s
Ki
0.00003 m²/s²
Anti-windup
On
Extra drain from 30 s
0 m³/s
  1. APreset, exactly as the link opens it.
  2. BChange only: Linearization height h₀ → 1 m, Initial height → 1 m.
  3. CChange only: Linearization height h₀ → 1.5 m, Initial height → 1.5 m. (ext.)

1. Predict

Does the water level return on the same time scale at low and high operating heights?

What happens

The local time constant is 2A√h₀/c and the local DC gain is 2√h₀/c. At a higher level, the same incremental inflow has a larger steady height effect and a slower local decay rate. This follows from the slope of √h; it is not a change in tank area. The display reports the local time constant, not an exact global settling time.

2. Observe

QuantityWhere to read itABC ext.
Local time constant τ₀ = 2A√h₀/c (s)Settings panel47.14 s66.667 s81.65 s
Height change from the start at t = 30 s (m)Readout at 30 s0.04459 m0.0484 m0.05026 m
Height change from the start at t = 120 s (m)Readout at 120 s0.08945 m0.1129 m0.1269 m

Values computed by State-feedback, tank and RLC engine 1.0.0 at the settings above. A replay readout can differ in the last digit if the slider is not exactly at the stated time; values read from a plot are approximate.

3. Explain

  1. For the same Δq, which run's level has risen more by 120 s?

    Run B: 0.1129 m against 0.08945 m. The local gain 2√h₀/c grows with the operating height, so the same extra inflow raises a high level further.

  2. Compare the local time constants, then the rise at 30 s. Why are the early rises so similar?

    τ₀ = 47.14 s at the lower level and 66.667 s at the higher. At first both tanks fill at Δq/A because the outflow has not changed yet, so by 30 s they have risen 0.04459 m and 0.0484 m. The difference builds up later, at the slower local rate of the higher level.

Extension (optional)

Set the operating and initial height to 1.5 m (run C). Predict τ₀ and the rise at 120 s.

τ₀ = 81.65 s and the level rises 0.1269 m by 120 s: slower and larger again, following √h₀.

Source: eigenroom.com/worksheets/tank/tank-operating-point/answersCite: EIGENROOM. (2026). The same tank has different time scales [Lab worksheet]. Accessed YYYY-MM-DD. https://eigenroom.com/worksheets/tank/tank-operating-point