EIGENROOMLAB WORKSHEET 30Thermal control
Off does not mean cold
NameSectionDate
Goal
Show that a heater cannot cool, and measure passive cooling with the time constant τ = C/H.
Setup
Lab eigenroom.com/lab/thermal?lesson=passive-cooling · short link eigenroom.com/passive-cooling
Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:
- Heat capacity C
- 1000 J/K
- Heat loss H
- 5 W/K
- Ambient Ta
- 20 °C
- Initial temperature
- 80 °C
- Target temperature
- 30 °C
- Maximum heater
- 400 W
- Controller
- PI
- Kp
- 20 W/K
- Ki
- 0.1 W/(K·s)
- Conditional anti-windup
- On
- Event
- No event
- Duration
- 900 s
- APreset, exactly as the link opens it.
- BChange only: Kp → 80 W/K.
- CChange only: Heat loss H → 10 W/K.
Pin each run before you change a setting, so you can compare runs at the same replay time.
1. Predict
Start at 80 °C and ask for 30 °C. Can increasing Kp make cooling faster once heater power is already zero?
Write your prediction and a reason before you run anything.
2. Observe
Read each value in the lab and write it in the table.
| Quantity | Where to read it | A | B | C |
|---|---|---|---|---|
| Time constant τ = C/H (s) | Settings panel | |||
| Requested power at t = 100 s (W) | Readout at 100 s | |||
| Applied power at t = 100 s (W) | Readout at 100 s | |||
| Temperature at t = 100 s (°C) | Readout at 100 s | |||
| Temperature at t = 200 s (°C) | Readout at 200 s | |||
| Gap left to ambient at t = 200 s, (T − Ta)/(T0 − Ta) (%) | Readout at 200 s |
3. Explain
Why are runs A and B identical during the first 200 s?
Check run A at t = τ: how much of the initial gap to ambient is left?
Run C doubles the heat loss. What changes besides faster cooling?
Extension (optional)
Set the target to 15 °C, below ambient. What does the controller do, and where does the temperature end?