EIGENROOMLAB WORKSHEET 30ANSWER KEY · FOR INSTRUCTORSThermal control

Off does not mean cold

Goal

Show that a heater cannot cool, and measure passive cooling with the time constant τ = C/H.

Setup

Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:

Heat capacity C
1000 J/K
Heat loss H
5 W/K
Ambient Ta
20 °C
Initial temperature
80 °C
Target temperature
30 °C
Maximum heater
400 W
Controller
PI
Kp
20 W/K
Ki
0.1 W/(K·s)
Conditional anti-windup
On
Event
No event
Duration
900 s
  1. APreset, exactly as the link opens it.
  2. BChange only: Kp → 80 W/K.
  3. CChange only: Heat loss H → 10 W/K.
  4. DChange only: Target temperature → 15 °C. (ext.)

1. Predict

Start at 80 °C and ask for 30 °C. Can increasing Kp make cooling faster once heater power is already zero?

What happens

At zero applied power, T = Ta + (T0 − Ta) exp(−t/τ), with τ = C/H. Larger Kp cannot make the input negative. Larger H speeds passive cooling but also raises the power needed to hold a warm target. This lumped model has no heater residual heat, sensor lag or transport delay; it is not an oven safety simulator.

2. Observe

QuantityWhere to read itABCD ext.
Time constant τ = C/H (s)Settings panel200.00 s200.00 s100.00 s200.00 s
Requested power at t = 100 s (W)Readout at 100 s-527.84 W-2111.35 W-241.46 W-827.84 W
Applied power at t = 100 s (W)Readout at 100 s0.00 W0.00 W0.00 W0.00 W
Temperature at t = 100 s (°C)Readout at 100 s56.39 °C56.39 °C42.07 °C56.39 °C
Temperature at t = 200 s (°C)Readout at 200 s42.07 °C42.07 °C28.45 °C42.07 °C
Gap left to ambient at t = 200 s, (T − Ta)/(T0 − Ta) (%)Readout at 200 s36.79%36.79%14.09%36.79%

Values computed by Thermal engine 1.0.0 at the settings above. A replay readout can differ in the last digit if the slider is not exactly at the stated time; values read from a plot are approximate.

3. Explain

  1. Why are runs A and B identical during the first 200 s?

    Both request negative power (-527.84 W and -2111.35 W at 100 s), but a heater cannot cool: the applied power is 0.00 W in both, so the body cools passively at the same rate.

  2. Check run A at t = τ: how much of the initial gap to ambient is left?

    τ = 200.00 s; at 200 s the temperature is 42.07 °C, so 36.79% of the gap remains, close to e⁻¹ as T = Ta + (T0 − Ta)e^(−t/τ) predicts.

  3. Run C doubles the heat loss. What changes besides faster cooling?

    τ halves to 100.00 s, so it reaches 28.45 °C by 200 s. But holding a warm target now needs more power: 100.00 W at the target against 50.00 W.

Extension (optional)

Set the target to 15 °C, below ambient. What does the controller do, and where does the temperature end?

It keeps requesting negative power the heater cannot give. The temperature approaches ambient and ends -5.67 °C from the target: a target below ambient cannot be held with heating alone.