EIGENROOMLAB WORKSHEET 27Thermal control
Give the thermostat a band
NameSectionDate
Goal
Measure how a thermostat's hysteresis band trades relay switching against temperature swing.
Setup
Lab eigenroom.com/lab/thermal?lesson=thermostat · short link eigenroom.com/thermostat
Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:
- Heat capacity C
- 1000 J/K
- Heat loss H
- 5 W/K
- Ambient Ta
- 20 °C
- Initial temperature
- 20 °C
- Target temperature
- 60 °C
- Maximum heater
- 400 W
- Controller
- ON-OFF
- Total hysteresis band
- 2 °C
- Event
- No event
- Duration
- 900 s
- APreset, exactly as the link opens it.
- BChange only: Total hysteresis band → 0 °C.
- CChange only: Total hysteresis band → 6 °C.
Pin each run before you change a setting, so you can compare runs at the same replay time.
1. Predict
A heater can only be fully on or off. How can it maintain 60 °C when 400 W is too much and 0 W is too little?
Write your prediction and a reason before you run anything.
2. Observe
Read each value in the lab and write it in the table.
| Quantity | Where to read it | A | B | C |
|---|---|---|---|---|
| Relay transitions | Results below the plots | |||
| Temperature swing, 600–900 s (max − min) (°C) | Plot, with the replay cursor | |||
| Time within ±1 °C (%) | Results below the plots | |||
| Heater energy (Wh) | Results below the plots |
3. Explain
How does the band trade relay transitions against temperature swing?
Why does even the zero band not hold the target exactly?
Extension (optional)
Heater energy hardly changes between the three runs. Why does the band not change energy use much?