EIGENROOMLAB WORKSHEET 27Thermal control

Give the thermostat a band

NameSectionDate

Goal

Measure how a thermostat's hysteresis band trades relay switching against temperature swing.

Setup

Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:

Heat capacity C
1000 J/K
Heat loss H
5 W/K
Ambient Ta
20 °C
Initial temperature
20 °C
Target temperature
60 °C
Maximum heater
400 W
Controller
ON-OFF
Total hysteresis band
2 °C
Event
No event
Duration
900 s
  1. APreset, exactly as the link opens it.
  2. BChange only: Total hysteresis band → 0 °C.
  3. CChange only: Total hysteresis band → 6 °C.

Pin each run before you change a setting, so you can compare runs at the same replay time.

1. Predict

A heater can only be fully on or off. How can it maintain 60 °C when 400 W is too much and 0 W is too little?

Write your prediction and a reason before you run anything.

2. Observe

Read each value in the lab and write it in the table.

QuantityWhere to read itABC
Relay transitionsResults below the plots
Temperature swing, 600–900 s (max − min) (°C)Plot, with the replay cursor
Time within ±1 °C (%)Results below the plots
Heater energy (Wh)Results below the plots

3. Explain

  1. How does the band trade relay transitions against temperature swing?

  2. Why does even the zero band not hold the target exactly?

Extension (optional)

Heater energy hardly changes between the three runs. Why does the band not change energy use much?

Source: eigenroom.com/worksheets/thermal/thermostatCite: EIGENROOM. (2026). Give the thermostat a band [Lab worksheet]. Accessed YYYY-MM-DD. https://eigenroom.com/worksheets/thermal/thermostat