EIGENROOMLAB WORKSHEET 27ANSWER KEY · FOR INSTRUCTORSThermal control

Give the thermostat a band

Goal

Measure how a thermostat's hysteresis band trades relay switching against temperature swing.

Setup

Open it on a phone or a computer; there is nothing to log in to or install. The link loads run A's settings:

Heat capacity C
1000 J/K
Heat loss H
5 W/K
Ambient Ta
20 °C
Initial temperature
20 °C
Target temperature
60 °C
Maximum heater
400 W
Controller
ON-OFF
Total hysteresis band
2 °C
Event
No event
Duration
900 s
  1. APreset, exactly as the link opens it.
  2. BChange only: Total hysteresis band → 0 °C.
  3. CChange only: Total hysteresis band → 6 °C.

1. Predict

A heater can only be fully on or off. How can it maintain 60 °C when 400 W is too much and 0 W is too little?

What happens

This model needs 5 × (60 − 20) = 200 W at the target. ON-OFF control alternates 400 W and 0 W. With a 2 °C band it turns on at 59 °C, off at 61 °C, and remembers its state between them. A wider band usually reduces transitions here but permits a larger temperature swing. Even a zero band switches only at the fixed 1 s controller ticks; it is not an infinitely fast relay.

2. Observe

QuantityWhere to read itABC
Relay transitionsResults below the plots6976125
Temperature swing, 600–900 s (max − min) (°C)Plot, with the replay cursor2.20 °C0.20 °C6.19 °C
Time within ±1 °C (%)Results below the plots77.51%85.14%27.78%
Heater energy (Wh)Results below the plots57.56 Wh57.67 Wh58.56 Wh

Values computed by Thermal engine 1.0.0 at the settings above. A replay readout can differ in the last digit if the slider is not exactly at the stated time; values read from a plot are approximate.

3. Explain

  1. How does the band trade relay transitions against temperature swing?

    Run B (0 °C band): 761 transitions and a 0.20 °C swing late in the run. Run A (2 °C): 69 and 2.20 °C. Run C (6 °C): 25 and 6.19 °C. A wider band switches less but lets the temperature wander further.

  2. Why does even the zero band not hold the target exactly?

    The relay can switch only at the 1 s controller ticks, and the heater is either 400 W or off while the target needs 200.00 W. Between ticks the temperature keeps moving, so a 0.20 °C swing remains.

Extension (optional)

Heater energy hardly changes between the three runs. Why does the band not change energy use much?

Over a long run the heater must replace the heat lost near the target, 200.00 W at the target itself, so the energies are close: 57.56 Wh, 57.67 Wh and 58.56 Wh. The wide band ends warmer (final error -2.88 °C), which costs a little more.

Source: eigenroom.com/worksheets/thermal/thermostat/answersCite: EIGENROOM. (2026). Give the thermostat a band [Lab worksheet]. Accessed YYYY-MM-DD. https://eigenroom.com/worksheets/thermal/thermostat